[Source : Korea National Fire Data Center]
Compact fire suppression device that automatically detects and
extinguishes fires in small, confined spaces
Extinguishing agent discharge port
Fully sealed container design
Lightweight and small-scale, designed for use with cabinet-type panel boards, etc.
Automatic heat-convection detection
Halogenated Extinguishing Agent
For electrical enclosures at risk of overheating fires—DB/SB/CP/MPP, MCC, UPS, Telecom Cab., Battery Cab., INV/CONV, ESS Cab.—and HVAC ODU. Ideal for enclosed/semi-enclosed spaces to contain fire spread.

Semi-permanent Service Life
US PATENT
Made in Korea Precision hand-finished
Temp. detection for all models
KC Mark KFI Type Approval
K-Mark certified
Rapid response in 1–3 seconds
Automatic discharge
Simple installation
Multi Option (monitoring system)
Established track record with certified performance
for 6 years since product launch
Installation Method : Flexible top mounting
KTL Certification : PB12021-016
![]() |
![]() |
![]() |
![]() |
|---|---|---|---|
| Classification | FL-XT 40 | FL-XT 120 | FL-XT 360 |
| Equipment Categories | Fire Extinguishing Equipment for Small Spaces | ||
| Fire Test Model | 300 x 200 x 700 | 400 x 300 x 1000 | 600 x 500 x 1200 |
| KFI Design Protected Volume(㎥) | 0.03 | 0.08 | 0.25 |
| K-Mark Protected Volume(㎥) | 0.04 | 0.12 | 0.36 |
| Fire Detection | Glass Bulb | ||
| Operating Temperature | 68℃ | ||
| Ambient Operating Temperature | -20~50℃ | ||
| Service Life | Semi-permanent | ||
Installation Method : Vertically on the top side
![]() |
![]() |
![]() |
![]() |
|---|---|---|---|
| Classification | FL-XT 360G | FL-XT 1200 | FL-XT 3000 |
| Equipment Categories | Automatic Gas Fire Extinguishing System | ||
| Fire Test Model | 600 x 600 x 1,000 | 900 x 900 x 1,500 | 1,200 x 1,200 x 2,000 |
| KFI Design Protected Volume(㎥) | 0.36 | 1.215 | 2.88 |
| Fire Detection | Glass Bulb | ||
| Operating Temperature | 68℃ | ||
| Ambient Operating Temperature | -20~50℃ | ||
| Service Life | Semi-permanent | ||
Installation Method : Vertically on the top side
![]() |
![]() |
![]() |
|---|---|---|
| Classification | FL-XT 6000 | FL-XT 10000 |
| Equipment Categories | Automatic Gas Fire Extinguishing System | |
| Fire Test Model | 1,500 x 1,500 x 2,500 | 1,800 x 1,800 x 3,000 |
| KFI Design Protected Volume(㎥) | 5.625 | 9.72 |
| Fire Detection | Glass Bulb | |
| Operating Temperature | 68℃ | |
| Ambient Operating Temperature | -20~50℃ | |
| Service Life | Semi-permanent | |
| Small Cm | Medium Cm | Large Cm | ||||
|---|---|---|---|---|---|---|
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
| FL-XT 40 | FL-XT 120 | FL-XT 360 | FL-XT 1200 | FL-XT 3000 | FL-XT 6000 | FL-XT 10000 |
| Protected Volume 0.04m³ |
Protected Volume 0.12m³ |
Protected Volume 0.36m³ |
Protected Volume 1.215m³ |
Protected Volume 2.880m³ |
Protected Volume 5.625m³ |
Protected Volume 9.72m³ |
The FL-XT automatic fire suppression system provides real-time monitoring of fire incidents and system anomalies. Upon detecting any irregularities, it promptly sends out alerts via system displays, SMS, WhatsApp, Messenger, email.
Monitoring systemProcess
| Before | During | After |
|---|---|---|
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
||||
| U.S. Patent Certificate | ||||
![]() |
![]() |
![]() |
![]() |
|
![]() |
![]() |
![]() |
![]() |
|
![]() |
![]() |
![]() |
![]() |
|